Fire Code Inspections
Fire Safety Code inspections are required in all commercial properties and all residential occupancies, other than single- and two-family homes.
The following is a list of some basic Fire Code requirements.
FIRE ALARM AND SPRINKLER SYSTEMS:
- Documentation showing fire alarm system testing and servicing shall be provided. Fire alarm systems shall be maintained in accordance with NFPA 72 requirements.
- Documentation showing sprinkler system testing and servicing shall be provided. Sprinkler systems shall be maintained in accordance with NFPA 25 requirements.
EXIT SIGNS:
- All exit signs shall be properly illuminated.
- All batteries for backup power shall be fully functional.
FIRE EXTINGUISHERS:
- All fire extinguishers require annual service and shall have current year inspection tags attached at all times.
- All fire extinguishers shall be properly wall-mounted.
EMERGENCY LIGHTS:
- All emergency lights shall be in proper working order.
- All emergency lights shall be tested once a month for 30 seconds and once a year for 90 minutes. Documentation of testing shall be kept on premise.
EXIT DOORS:
- All exit doors and access to said doors shall be kept clear and free of all obstructions.
- All exit doors shall be free of deadbolts, slide bolts and padlocks. Only one locking mechanism is permitted per door.
COMMERCIAL COOKING ESTABLISHMENTS:
- Provide documentation for semi annual hood and duct cleaning. Hood and duct maintenance shall be in accordance with NFPA 96 requirements.
- Provide documentation that fire suppression systems have been tested and serviced every six months as required by NFPA 17 & 17A standards.
PLEASE NOTE: THE ABOVE IS A LIST OF BASIC FIRE CODE REQUIREMENTS; OTHER VIOLATIONS MAY BE IDENTIFIED UPON INSPECTION.